男生女生一起差差差大全视频,无码高潮爽到爆的喷水视频,国内精品久久久久精品可下,成年奭片免费观看午夜

Loading...

GCK
Category:Low voltage switchgear
Release date:2019-02-28 13:02:23
 

1. Product introduction
GCK low-voltage withdrawable switchgear (hereinafter referred to as switchgear) is suitable for three-phase AC 50 (60) Hz, rated voltage 380V, 660V, rated current 4000A and below three-phase four-wire system and three-phase five-wire power system. It is suitable for power users and power systems in power plants, substations, industrial and mining enterprises, building hotels, airports, terminals, etc. for power distribution and motor control.

2, structural characteristics
2.1 The device is compact and accommodates more functional units in a smaller space.
5.2 Strong versatility and flexible assembly: C-shaped or reinforced C-profiles with a modulus of 25 mm are assembled to meet various structural forms, protection levels and operating environments.
5.3 Adopt standard module design: It can be assembled into standard units such as protection, operation, conversion, control, adjustment, measurement and indication. Users can choose assembly according to their needs to form frame structure and rawer unit of different schemes.
2.4 Safe and reliable: the structural parts inside the cabinet are galvanized and purified, and the door panels and side panels around the cabinet are electrostatically sprayed. Both strong mechanical strength and reliable insulation protection.
2.5 Easy to disassemble: no special complicated tools are needed

  3, basic technical parameters

Serial number parameter name Technical Parameters
1 Rated insulation voltage AC660V,AC1000V
2 Rated operating voltage AC380V,AC660V
3 Horizontal busbar rated current 400A,630A,800A,1000A,1250A,1600A,2000A,2500A,3200A,4000A
4 Vertical busbar rated current 1000A
5 Feed circuit maximum current 4000A
6 Drawer loop maximum current 800A
7 Control motor maximum capacity 320kW
8 Horizontal busbar peak withstand current (0.1s) 63kA 105kA 176kA 220kA
9 Horizontal busbar short-time withstand current (1s) 30kA 50kA 80kA 100kA
10 Vertical busbar peak withstand current (0.1s) 63kA 105kA
11 Vertical busbar short-time withstand current (1s) 30kA 50kA
12 Rated power frequency withstand voltage (5s) 2500V
13 *Enclosure rating IP30,IP40
14 Shell size (mm) Width 600 × (800, 1000) × depth 800 (1000) × height 2200

Note: * When ordering the IP45 enclosure protection level, please consult with our company.